Prestige

TM

Installation Guide

6

69-2057EFS—03

1H/1C Heat Pump [

8

]

C

24VAC common

R

Power [

1

]

Rc

[R+Rc joined by jumper]

O/B

Changeover valve [

7

]

Y

Compressor contactor

**

G

Fan relay

**

2H/1C Heat Pump [

9

]

C

24VAC common

R

Power [

1

]

Rc

[R+Rc+Rh joined by jumper]

O/B Changeover valve [

7

]

Aux Auxiliary heat relay
Y

Compressor contactor

**

G

Fan relay

**

L

Relay [

12

]

2H/2C Heat Pump [

10

]

C

24VAC common

R

Power [

1

]

Rc

[R+Rc joined by jumper]

O/B

Changeover valve [

7

]

Y

Compressor contactor (stage 1)

**

Y2

Compressor contactor (stage 2)

G

Fan relay

**

3H/2C Heat Pump [

11

]

C

24VAC common

R

Power [

1

]

Rc

[R+Rc joined by jumper]

O/B Changeover valve [

7

]

Aux Auxiliary heat relay
Y

Compressor contactor (stage 1)

**

Y2

Compressor contactor (stage 2)

G

Fan relay

**

L

Relay [

12

]

Heat pump systems

System-specific wiring guides

**

[See note on bottom of page 4]

[

1

] Power supply. Provide disconnect means and overload protection as required.

[

2

] Remove jumper (R to Rc) for systems with two transformers. Common connection must come

from cooling transformer.

[

3

] In Installer Setup, set system type to Heat Only, No Fan.

[

4

] In Installer Setup, set system type to Conventional with zero cooling stages.

[

5

] In Installer Setup, set system type to Conventional with zero heat stages.

[

6

] In Installer Setup, set system type to Conventional with 2 heat AND 2 cool stages.

[

7

] In Installer Setup, set changeover valve to O or B.

[

8

] In Installer Setup, set to Heat Pump with 1 compressor stage and no auxiliary heat stages.

[

9

] In Installer Setup, set to Heat Pump with 1 compressor stage and 1 auxiliary heat stage.

[

10

] In Installer Setup, set to Heat Pump with 2 compressor stages and no auxiliary heat stages.

[

11

] In Installer Setup, set to Heat Pump with 2 compressor stages and 1 auxiliary heat stage.

[

12

] “L” terminal sends a continuous output when thermostat is set to Em. Heat, and acts as a

system monitor when in Heat, Cool or Off modes.

See [

notes

] below.