beautypg.com

Warning, Santa fe pellet insert, D. pipe selection chart – Hearth and Home Technologies Santa Fe Pellet Insert SANTAFEI-B User Manual

Page 13: C. equivalent feet of pipe

background image

R

September 1, 2008

7019-205C

Page 13

Santa Fe Pellet Insert

Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer
to the owner’s information manual provided with this appli-
ance. For assistance or additional information consult a
qualified installer, service agency or your dealer.

WARNING

The chart will help you in determing proper vent-
ing size according to the equivalent feet of pipe
calcuated above and the altitude above sea level
of this installation. Figure 13.2.

Locate the calculated equivalent feet of pipe on
the vertical left side of the chart. Move to the
right horizontally on the chart until you reach your
altitude above sea level.

If you fall below the diagonal line, 3 or 4 inch (76
to 102mm) pipe may be used. If it is anywhere
above the diagonal line, a 4 inch (102mm) diam-
eter pipe is required.

The chart reveals that a 90° elbow is 5 times as
restrictive to the flow of exhaust gases under posi-
tive pressure as 1 foot of horizontal pipe, and a
foot of horizontal pipe is twice as restrictive as a
foot of vertical pipe.

D. Pipe Selection Chart

The table below can help you calculate the equivalent feet
of pipe which is a method used to determine pellet vent size.
Figure 13.1.

C. Equivalent Feet of Pipe

2 ft.

2 ft.

3 ft.

2 ft.

Example of 3 Elbow-Rear Vent Termination Calculation

Figure 13.1

Figure 13.2

Pellet Venting

Component

# of

Elbows

Feet of

Pipe

Multiplied

By

Equivalent

Feet

Components

Equivalent Feet

90

o

Elbow or Tee

3

X

5

15

45

o

Elbow

X

3

Horizontal Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

Note: This is a generic example and is not
intended to represent any specific fuel type.

3 in. or 4 in. (76mm or 102mm) Diameter Pipe

Equivalent Pipe

Length In Feet

ALTITUDE IN THOUSANDS OF FEET

0

20

30

1 2 3 4 5 6 7 8 9 10

4 in. (102mm) Diameter Pipe Only

10

Example 1

Example 2

Example 1: If the equivalent length of pipe is 23 feet with altitude of
8,000 feet you must use 4 inch (102mm) diameter type “L” or “PL”
vent.

Example 2: If the equivalent length of pipe is 12 feet with altitude of
6,000 feet you may use 3 or 4 inch (76 to 102mm) diameter type “L”
or “PL” vent