E) harvest cycle, F) shutdown, E) harvest cycle f) shutdown – Hoshizaki KM-2500SWH3 User Manual
Page 13

13
e) Harvest Cycle
Same as the initial harvest cycle. See "II.B.1.b) Initial Harvest Cycle."
Note: Unit continues to cycle until BC is satisfied or power is turned off. The unit always
restarts at the 1-minute fill cycle.
f) Shutdown
When ice contacts the thermostatic bulb (BC switch open), BC shuts down the unit within
10 seconds. BC is factory set, and generally no adjustment is required. However,
adjustment may be needed in some conditions, particularly at higher altitude
locations.
CAUTION! Do not adjust S4 dip switch 7 out of the factory default
position on this model. This dip switch must be left in the factory default position
or this unit will not operate correctly.
Legend:
BC–bin control; CB–control board; Comp–compressor; FMR–fan
motor-remote;
F/S–float switch; HGV–hot gas valve; LLV–liquid line valve;
PM–pump motor; WV–inlet water valve