C. performance data, Km-2500swh3 (water-cooled) – Hoshizaki KM-2500SWH3 User Manual
Page 26
26
C. Performance Data
1. KM-2500SWH3 (water-cooled)
Note:
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold
should be used for reference only.
2. We reserve the right to make changes in specifications and design without prior
notice.
70/21
2408
1092
2395
1087
2256
1024
80/27
2398
1088
2379
1079
2172
985
90/32
2395
1087
2365
1073
2184
991
lbs./day kg./day
100/38
2327
1055
2323
1054
2018
915
70/21
80/27
90/32
watts
100/38
70/21
2174
8.23
2372
8.98
2679
10.14
80/27
2325
8.80
2631
9.96
2959
11.20
90/32
2372
8.98
2847
10.78
3173
12.01
gal./day m
3
/day
100/38
2685
10.16
2924
11.07
3473
13.15
70/21
80/27
90/32
min.
100/38
70/21
80/27
90/32
min.
100/38
70/21
245
17.2
250
17.6
272
19.1
80/27
249
17.5
256
18.0
287
20.2
90/32
250
17.6
261
18.4
289
20.3
PSIG kg/cm
2
G
100/38
259
18.2
267
18.8
314
22.1
70/21
39
2.7
40
2.8
42
3.0
80/27
39
2.8
40
2.8
44
3.1
90/32
40
2.8
41
2.9
44
3.1
PSIG kg/cm
2
G
100/38
41
2.9
42
2.9
47
3.3
35,500 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
TOTAL HEAT OF REJECTION FROM COMPRESSOR
4,900 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)]
WATER FLOW FOR CONDENSER
130 gal./h [AT 100ºF (38ºC) / WT 90ºF (32ºC)]
PRESSURE DROP OF COOLING WATER LINE
less than 10 PSIG
Note: Pressure data is recorded at 5 minutes into freezing cycle.
The data not in
bold
should be used for reference only.
25
24
26
24
25
26
4.4
3.1
4.6
APPROXIMATE WATER
CONSUMPTION PER 24 HR.
FREEZING CYCLE TIME
HARVEST CYCLE TIME
3566
24
24
3510
3557
3572
3727
APPROXIMATE ICE
PRODUCTION PER 24 HR.
APPROXIMATE ELECTRIC
CONSUMPTION
3572
3653
3720
WATER TEMP. (ºF/ºC)
AMBIENT TEMP.
(ºF/ºC)
50/10
70/21
90/32
3615
3673
3751
3780
26
27
28
30
HEAD PRESSURE
4.1
3.6
4.4
2.9
2.7
3.1
5.0
3.8
3.7
TOTAL HEAT OF REJECTION FROM CONDENSER
SUCTION PRESSURE
ENG.F-011.1.0205