Low ice production – Hoshizaki CUBELET ICEMAKER/DISPENSER DCM-750BAH-OS User Manual

Page 41

background image

4

Problem

Possible Cause

Remedy

[5] All components

run, but no ice is
produced. (continued)

d) Evaporator

. Defective.

. Replace.

e) Water Supply Line

(water-cooled model
only)

. Condenser water

pressure too low or
off and high pressure
control opens and
closes frequently.

. Check and get

recommended pressure.

f) Water Regulating Valve

(water-cooled model
only)

. Water regulating

valve set too high or
clogged (water-cooled
model only).

. Clean, adjust, or replace.

2. Low Ice Production

Problem

Possible Cause

Remedy

[] Low ice production.

a)Evaporator

. Dirty or defective.

. Clean or replace.

b)Bin Control

. Erratic, sticking,

defective.

. Clean or replace.

c) Drain Valve

. Leaking water.

. Clean or replace.

d)Expansion Valve

. Bulb loose.

. Secure bulb.

. Operating erratically.

. Check and replace.

e)Refrigerant Charge

. Low charge.

. See "V.B. Service for

Refrigerant Lines."

. Overcharge.

. See "V.B. Service for

Refrigerant Lines."

f) Refrigerant Line

. Refrigerant line or

component restricted.

. Repair/replace the

clogged line/component
and replace the drier.

g)High-Side Pressure

Too High

. Dirty air filter or

condenser.

. Clean.

. Ambient (or

condenser) water
temperature too warm.

. Reduce temperature.

3. Fan motor slow rpm.

3. See "3. [] a) Fan Motor."

4. Fan motor capacitor.

4. Check and replace.

5. Condenser water

pressure too low or off
(water-cooled model
only).

5. Check and get

recommended pressure.

6. Water regulating

valve set too high or
clogged (water-cooled
model only).

6. Clean, adjust, or replace.

h)Compressor

. Inefficient compressor. . Replace
. Faulty thermal

protector (overload).

. Replace compressor.

3. Faulty capacitor/

starter.

3. Replace.