“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–46
13
USP
Unattended Start
Protection
ON
ON powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
ON powerup, the inverter will resume a RUN
command that was active before power loss
14
CS
Commercial Power
Source
ON
OFF-to-ON transition signals the inverter that the
motor is already running at powerup (via bypass),
thus suppressing the inverter’s motor output in Run
Mode
OFF
ON-to-OFF transition signals the inverter to apply a
time delay (B003), frequency match its output to
existing motor speed, and resume normal Run Mode
operation
15
SFT
Software Lock
ON
The keypad and remote programming devices are
prevented from changing parameters
OFF
The parameters may be edited and stored
16
AT
Analog Input Voltage/
current Select
ON
Terminal [OI] is enabled for current input (uses
terminal [L] for signal return)
OFF
Terminal [O] is enabled for voltage input (uses
terminal [L] for signal return)
18
RS
Reset Inverter
ON
The trip condition is reset, the motor output is turned
OFF, and powerup reset is asserted
OFF
Normal power-on operation
20
STA
START
(3-wire interface)
ON
Starts the motor rotation
OFF
No change to present motor status
21
STP
STOP
(3-wire interface)
ON
Stops the motor rotation
OFF
No change to present motor status
22
F/R
FWD, REV
(3-wire interface)
ON
Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction.
OFF
Selects the direction of motor rotation: OFF =REV.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction.
23
PID
PID Disable
ON
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=1).
OFF
Has no effect on PID loop operation, which operates
normally if PID Enable is active (A071 = 1).
24
PIDC
PID Reset
ON
Resets the PID loop controller. The main conse-
quence is that the integrator sum is forced to zero.
OFF
No effect on PID loop controller
27
UP
Remote Control
UP Function (motor-
ized speed pot.)
ON
Accelerates (increases output frequency) motor from
current frequency
OFF
No change to output frequency
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description