2. Low Ice Production

Problem

Possible Cause

Remedy

[1] Low ice production.

a)Evaporator

1. Dirty.

1. Clean. See "VI.A.

Cleaning and Sanitizing
Instructions."

b)Bin Control

1. Erratic, sticking,

defective.

1. See "IV.D. Bin Control

Check."

c) Losing Water

1. Drain valve leaking.

1. Clean or replace.

2. Mechanical seal

leaking.

2. Replace.

3. O-ring leaking.

3. Replace.

d)Expansion Valve (TXV)

(not adjustable)

1. Low-side pressure too

low.

1. Replace.

2. Low-side pressure too

high.

2. See if expansion valve

bulb is mounted properly,
and replace the valve if
necessary.

e)Refrigerant Line

1. Gas leaks.

1. Check for leaks with a leak

detector. Repair leaks.
Replace drier and charge
with refrigerant. See "V.A.
Service for Refrigerant
Lines."

2. Refrigerant lines or

components restricted

2. Remove the restriction or

component and replace
the drier.

3. Overcharged.

3. Recharge.

f) High-Side Pressure

Too High

1. Dirty air filter or

condenser.

1. Clean.

2. Ambient or condenser

water temperature too
warm.

2. Reduce temperature.

3. Fan motor slow rpm.

3. See "3.[2]a) Fan Motor".

4. Fan motor capacitor.

4. Check and Replace.

5. Condenser water

pressure too low or off
(water-cooled model).

5. Check and get

recommended pressure.

6. Water regulating

valve restricted
(water-cooled model).

6. Clean.

g)Compressor

1. Inefficient compressor. 1. Replace compressor.
2. Faulty thermal

protector (overload).

2. Replace compressor.

3. Faulty capacitor/

starter.

3. Replace components.