beautypg.com

Quickspecs – HP ProLiant DL380 User Manual

Page 46

background image

HP 1200W Power Supply
Part Number - AC

500172-B21

Operational Input Voltage
Range (Vrms)

100 to 240

Frequency Range (Nominal)
(Hz)

50/60

Nominal Input Voltage (Vrms)

100

120

208

200

220

230

240

Maximum Rated Output Wattage

800

900

1200

1200

1200

1200

1200

Nominal Input Current (A rms)

9.7

9.0

7.0

6.8

6.4

9.1

5.9

Max Rated Input Wattage Rating
(Watts)

930

1034

1348

1348

1348

1348

1348

Max. Rated VA (Volt-Amp)

970

1079

1406

1406

1406

1406

1406

Efficiency (%) at Max. Rated
Output Wattage

86

87

89

89

89

89

89

Power Factor

0.97

0.97

0.97

0.97

0.97

0.97

0.97

Leakage Current (mA)

0.42

0.50

0.83

0.87

0.92

0.96

1.00

Max. Inrush Current (A peak)

30

30

30

30

30

30

30

Max. Inrush Current duration
(mS)

20

20

20

20

20

20

20

Maximum British Thermal Unit
Rating (BTU-Hr)

3174

3530

4600

4600

4600

4600

4600

HP 1200W PSU 48VDC Input Part Number

437573-B21

Input Voltage Range (DCV)

36-72

Frequency Range (Nominal) (Hz)

DC

Nominal Input Voltage (VDC)

36

48

72

Maximum Rated Output Wattage

1200

1200

1200

Nominal Input Current (ACD)

38

28

19

Max Rated Input Wattage Rating (Watts)

1380

1350

1365

Max. Rated VA (Volt-Amp)

1380

1350

1365

Efficiency (%) at Max. Rated Output Wattage

87

89

88

Power Factor

N/A

N/A

N/A

Leakage Current (mA)

N/A

N/A

N/A

Max. Inrush Current (A peak)

20

25

35

Max. Inrush Current duration (mS)

1

1

3

Maximum British Thermal Unit Rating (BTU-Hr)

4713

4610

4662

NOTES: To review typical system power ratings use the HP Power Advisor which is available online located at url:

www.hp.com/go/proliant-energy-efficient

or

www.hp.com/go/hppoweradvisor

QuickSpecs

HP ProLiant DL380 Generation 6

Power Specifications

DA - 13234 Worldwide QuickSpecs — Version 16 — 8.28.2009