Combustible Wall Penetration
Frame a hole in a combustible wall for an interior wall
shield fi restop, (Figure 6.2) whenever a wall is penetrated.
Use same size framing materials as those used in the wall
construction. The wall shield fi restop maintains minimum
clearances and prevents cold air infi ltration.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncombus-
tible materials such as concrete, a hole with diameter one
inch greater than the pipe is acceptable.

B. Wall Penetration Framing

Figure 6.3 Exterior Wall Hole

* Shows center of vent framing hole for top or rear venting.

The center of the hole is one (1) inch (25.4 mm) above the

center of the horizontal vent pipe.

WALL

HEAT

SHIELD

HEAT

SHIELD

3 in. TOP

CLEARANCE

WALL

SHIELD

FIRESTOP

1 in. CLEARANCE
BOTTOM & SIDES

7 in.

A

B

C

D

*

*

A. Pipe Clearances to Combustibles

Vent Clearances and Framing

6

Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
specifi ed.
• Do not pack air space with insulation or other

materials.

Failure to keep insulation or other materials
away from vent pipe may cause fi re.

Figure 6.1 Pipe Clearances

1 in. CLEARANCE

AROUND VERTICAL

SECTIONS

3 in. TOP

CLEARANCE

1 in. SIDE AND

BOTTOM CLEARANCE

NOTE: Slope
not required.

WARNING

Figure 6.2 Horizontal Venting Clearances to Combustible Materials

A

B

C

D

SL-550TR-D

in.

36 1/2

24 3/8

35 1/2

23 3/8

mm

927

619

902

594

SL-750TR-D

in.

41

27 7/8

40

26 7/8

mm

1041

708

1016

683

SL-950TR-D

in.

44

31 7/8

43

30 7/8

mm

1118

810

1092

784

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
The heat shield is designed to be used on a wall 4 in. to 7-1/4 in. (102
mm to 184 mm) thick
. If wall thickness is less than 4 in. (102 mm) the
existing heat shields must be fi eld trimmed. If wall thickness is greater than
7-1/4 in. (184 mm) a DVP-HSM-B will be required.