Honeywell NXL User Manual
Page 68

68(96)
Control Keypad
Honeywell
Honeywell
Honeywell
Honeywell
7
7.4.7 System menu (S6)
The System menu can be entered from the main menu by pushing the Menu button right when the
location indication S6 is visible on the display.
The controls associated with the general use of the frequency converter, such as keypad settings, customised
parameter sets or information about the hardware and software are located under the System menu.
Below you will find a list of the functions available in the System menu.
Functions in the System menu
Code
Function
Min
Max
Unit
Default
Cust
Selections
S6.3
Copy parameters
P6.3.1
Parameter sets
0 = Select
1 = Store set 1
2 = Load set 1
3 = Store set 2
4 = Load set 2
5 = Load factory defaults
6 = Fault
7 = Wait
8 = OK
S6.5
Security
P6.5.2
Parameter lock
0
1
0
0 = Change Enabled
1 = Change Disabled
S6.6
Keypad settings
P6.6.1
Default page
0
1.1
P6.6.3
Timeout time
5
65535
s
1200
S6.7
Hardware settings
P6.7.2
Fan control
0
0
0 = Continuous
1 = Temperature (only
sizes MF4 and bigger)
P6.7.3
HMI acknowledg.
timeout
200
5000
ms
200
P6.7.4
HMI number of retries
1
10
5
S6.8
System info
S6.8.1
Counters menu
C6.8.1.1
MWh counter
KWh
C6.8.1.2
Operating days
counter
hh:mm:
ss
C6.8.1.3
Operating hours
counter
hh:mm:
ss
S6.8.2
Trip counters
T6.8.2.1
MWh trip counter
kWh
P6.8.2.2
Clear MWh trip
counter
0 = No action
1 = Clear MWh trip counter
T6.8.2.3
Operating days trip
counter