Battery Backup Operations

Figure 3-6

illustrates the two types of backup operations: backup mode and

destage mode.

Backup Mode (USP V and VM)

When backup mode is chosen and a power failure occurs, storage system

operations will continue normally for 200 milliseconds. If the power failure
exceeds 200 ms, the storage system uses power from the batteries to back

up the cache memory and shared memory for 36 hours or 48 hours,
depending on the amount of cache memory.

Destage Mode (USP V only)

When destage mode is chosen and a power failure occurs, storage system

operations will continue normally for 1 minute. If the power failure exceeds
1 minute, the storage system uses power from the batteries to destage the
data from cache memory onto the drives and back up the cache memory

and shared memory for 18 hours or 24 hours, depending on the amount of
cache memory.
Destage mode requires the 56V battery option (DKC-F610I-ABX).
Destage mode is not supported in the following cases:

When external storage is connected.

When Cache Residency Manager BIND mode is applied.

When cache memory capacity is 260 GB or larger.

Battery Charge

If the battery is not fully charged when a power failure occurs, the backup

processes are affected as follows:

Backup mode: The backup time becomes short (less than 36/48 hours).

Destage mode: The destage process may not be possible until the
battery charging is complete, and the backup time may also become
short (less than 18/24 hours).