Hitachi Universal Storage Platform VM User Manual

Page 85

background image

Functional and Operational Characteristics

3-41

Hitachi Universal Storage Platform V/VM User and Reference Guide

Detection of Power Failure

AC Input Power Failure Occurs

1 minute

Storage

System

Operating

8 minutes

Data destage process

Power off process

5 minutes

24 hours (CM up to 128 GB)
18 hours (CM 132 GB to 256 GB)

CM and SM are backed up by battery.

200 ms

Storage

System

Operating

CM and SM are backed up by battery.

Ç

*2

Destage Mode

USP V only

(battery option

required)

Ç

*1

Backup Mode

USP V/VM

Power Failure

Power Failure

Universal Storage Platform V:
48 hours: CM up to 128 GB
36 hours: CM 132 GB to 256 GB

Universal Storage Platform VM:
36 hours

Notes:
1. When power is recovered after a failure while backup power is being supplied by battery, the storage system

operates depending on the status of the Auto-Power-On JP on the Operator panel:
ENABLE: The storage system is powered on automatically.
DISABLE: The storage system is powered on by operating the Power ON/OFF switch or the PCI.

2. When power is recovered after a failure during the destage process, the destage and power-off processes are

executed.

Figure 3-6

Battery Backup Processes for Power Failure