THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

85

68-0311—02

Advanced Features

ADAPTIVE INTELLIGENT RECOVERY (RESIDENTIAL USE

ONLY)

Over time, the Prestige® thermostat “learns” how long it takes

your system to reach your programmed temperature setting.

The thermostat turns on the heating/cooling system early and

assures that the programmed temperature setting is reached at

the programmed time regardless of weather conditions. For

example, if the Wake program period is set to 6:00 am with a

heat setting of 70 degrees, the heat will turn on before 6:00

am, so the temperature is 70 degrees at 6:00 am. The

thermostat displays "In Recovery" when it turns the system on

early.

Adaptive Intelligent Recovery® calculates the recovery ramp

based on how far the room temperature is away from the

temperature setting, previous equipment performance and

weather history, allowing the thermostat to start recovery at the

optimal time so it can reach the programmed temperature

setting at the programmed time.

The Prestige® thermostat uses two recovery ramps when

setup to control a heat pump system. One ramp for the

compressor and one ramp for the auxiliary heat. Once the

room temperature intersects the compressor ramp, the

compressor turns on until the setpoint is reached. If the room

temperature does not rise quickly enough and intersects the

second ramp, the auxiliary heat turns on. It takes about one

week for the thermostat to adjust to weather conditions,

equipment performance and construction of the home. If the

temperature setting is reached too early or too late, the ramp is

adjusted for the next day's recovery. See Fig. 142.

Fig. 142.

DEHUMIDIFICATION AWAY MODE

Your system can be set to control indoor climate while your

home is vacant during the humid season. Before you leave,

touch MENU, then select Dehumidification Away Mode.

Temperature and humidity will be kept at levels that protect

your home and possessions. When you return, touch Cancel to

resume normal operation.

COMPRESSOR PROTECTION

The thermostat keeps the compressor off for a few minutes

before restarting, to prevent equipment damage. During this

“off” time, the message “waiting for equipment” is displayed on

screen.

PRE-OCCUPANCY PURGE (COMMERCIAL USE ONLY)

This feature turns on the fan 1 to 3 hours before each

“occupied” time period, to provide a comfortable workplace

when you arrive.

P + I CONTROL

A conventional mechanical or electronic thermostat does not

control temperature precisely at setpoint. Typically there is an

offset (droop) in the control point as the system load changes.

Many factors contribute to offset including the switch

differential, thermal lag, overshoot, cycle rates and system

load.

The Prestige® thermostat however, works much differently

than a conventional mechanical or electronic thermostat. The

proprietary algorithm in the thermostat eliminates the factors

causing offset (droop). This makes temperature control more

accurate than the conventional mechanical or electronic

thermostat. The temperature control algorithm is called

proportional plus integral (P + I) control.

The thermostat sensor or a remote indoor sensor senses the

current space temperature. The proportional error is calculated

by comparing the sensed temperature to the setpoint

temperature. The deviation from the setpoint is the proportional

error.

The thermostat also determines integral error, which is a

deviation based on the length of error time (how long the

sensed room temperature has been away from the setpoint

temperature). The sum of the two errors is the (P + I) error. The

cycle rate used to reach and maintain the setpoint temperature

is computed using the P + I control algorithm. The addition of

the integral error is what differentiates the thermostat from

many other mechanical and electronic thermostats. See Fig.

143.

Fig. 143.

WAKE

COMPRESSOR SETPOINT

AUXILIARY HEAT SETPOINT

ROOM TEMPERATURE

M6406A

HEATING

COOLING

PERCENT LOAD

TEMPERATURE

THERMOSTAT

HEAT SETPOINT

P+I CONTROL

POINT

PROPORTIONAL COOL

CONTROL POINT

THERMOSTAT

COOL SETPOINT

P+I CONTROL POINT

PROPORTIONAL HEAT

CONTROL POINT

M4414

100

50

0

50

100