Quickspecs, Hp integrity superdome servers: 16-way, 32-way, And 64-way – HP Integrity Superdome Server User Manual
Page 17: And 64-way configuration
Customer Provided Part
Customer Provided Part
Customer Provided Part
Customer Provided Part
PDCA Product
PDCA Product
PDCA Product
PDCA Product
Number
Number
Number
Number
Attached Power
Attached Power
Attached Power
Attached Power
Cord
Cord
Cord
Cord
Attached Plug
Attached Plug
Attached Plug
Attached Plug
In Line Connector
In Line Connector
In Line Connector
In Line Connector
Panel Mount
Panel Mount
Panel Mount
Panel Mount
Receptacle
Receptacle
Receptacle
Receptacle
A5800A Option 006 OLFLEX 190 (PN
600804), four-
conductor, 6-AWG
(16 mm
2
), 600- Volt,
60-Amp, 90- degree
C, UL, and CSA
approved, conforms
to CE directives
GN/YW ground wire.
Mennekes ME 460P9
3-phase, 4-wire, 60-
Amp, 250-Volt, UL-
approved. Color
blue, IEC 309-1, IEC
309-1, grounded at
3:00 o'clock.
Mennekes ME 460C9 3-
phase,
4-wire, 60-amp, 250-Volt,
UL-approved. Color blue,
IEC 309-1, IEC 309-1,
grounded at 9:00 o'clock.
a
Mennekes ME 460R9 3
phase,
4-wire, 60-amp, 250-Volt,
UL-approved. Color blue,
IEC 309-1, IEC 309-1,
grounded at 9:00 o'clock.
b
A5800A Option 007 Five conductors, 10-
AWG (6 mm
2
),
450/475-Volt, 32-
Amp,
European wire
cordage, GN/YW
ground wire.
Mennekes ME
532P6-14 3-phase,
5-wire, 32-Amp,
450/475-volt, VDE-
certified, color red,
IEC 309-1, IEC 309-
2, grounded at 6:00
o'clock.
Mennekes ME 532C6 16 3-
phase, 5-wire, 32-Amp,
450/475-Volt, VDE-
certified, color red, IEC
309-1, IEC 309-2,
grounded at 6:00 o'clock.
c
Mennekes ME532R6 1276
3-phase, 5-wire, 32-Amp,
450/475-Volt, VDE-
certified, color red, IEC
309-1, IEC 309-2,
grounded at 6:00 o'clock.
b
a. In line connector is available from HP by purchasing A6440A, Option 401.
b. Panel mount receptacles must be purchased by the customer from a local Mennekes supplier.
c. In line connector is available from HP by purchasing A6440A, Option 501.
NOTE:
NOTE:
NOTE:
NOTE: A qualified electrician must wire the PDCA in line connector to site power using copper wire and in compliance
with all local codes.
Input Requirements
Input Requirements
Input Requirements
Input Requirements
Reference the Site Preparation Guide for detailed power configuration requirements.
Requirements
Requirements
Requirements
Requirements
Value
Value
Value
Value
Conditions/Comments
Conditions/Comments
Conditions/Comments
Conditions/Comments
Nominal Input Voltage (VAC rms)
200/208/220/230/240
Input Voltage Range (VAC rms)
200-240
Auto selecting. Measure at input
terminals
Frequency Range (Hz)
50/60
Number of Phases
3
3-phase 5-wire with power cord;
3-phase 4-wire with power cord
Maximum Input Current (A rms), 3-
Phase 5-wire
20
3-phase source with a source voltage of
220 VAC measured phase to neutral
Maximum Input Current (A rms), 3-
Phase 4-wire
40
3-phase source with a source voltage of
either 208 VAC or 230 VAC measured
phase to phase
Maximum Inrush Current (A peak)
90
Circuit Breaker Rating (A),
3-Phase 5-wire
25 A
Per phase
Circuit Breaker Rating (A),
3-Phase 4-wire
45 A
Per phase
Power Factor Correction
0.95 minimum
Ground Leakage Current (mA)
>3.5 mA, with 6 BPSs installed
Warning label applied to the PDCA at
the AC Mains input
Cooling Requirements
Cooling Requirements
Cooling Requirements
Cooling Requirements
The cooling system in Superdome was designed to maintain reliable operation of the system in the specified
environment. In addition, the system is designed to provide redundant cooling (i.e. N+1 fans and blowers) that
allows all of the cooling components to be "hot swapped."
Superdome was designed to operate in all data center environments with any traditional room cooling scheme (i.e.
raised floor environments) but in some cases where data centers have previously installed high power density systems,
QuickSpecs
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
HP Integrity Superdome Servers: 16-way, 32-way,
and 64-way
and 64-way
and 64-way
and 64-way
Configuration
DA - 11717 Worldwide — Version 1 — June 30, 2003
Page 17