Quickspecs, Hp integrity superdome servers: 16-way, 32-way, And 64-way – HP Integrity Superdome Server User Manual

Page 17: And 64-way configuration

background image

Customer Provided Part

Customer Provided Part

Customer Provided Part

Customer Provided Part

PDCA Product

PDCA Product

PDCA Product

PDCA Product
Number

Number

Number

Number

Attached Power

Attached Power

Attached Power

Attached Power
Cord

Cord

Cord

Cord

Attached Plug

Attached Plug

Attached Plug

Attached Plug

In Line Connector

In Line Connector

In Line Connector

In Line Connector

Panel Mount

Panel Mount

Panel Mount

Panel Mount
Receptacle

Receptacle

Receptacle

Receptacle

A5800A Option 006 OLFLEX 190 (PN

600804), four-
conductor, 6-AWG
(16 mm

2

), 600- Volt,

60-Amp, 90- degree
C, UL, and CSA
approved, conforms
to CE directives
GN/YW ground wire.

Mennekes ME 460P9
3-phase, 4-wire, 60-
Amp, 250-Volt, UL-
approved. Color
blue, IEC 309-1, IEC
309-1, grounded at
3:00 o'clock.

Mennekes ME 460C9 3-
phase,
4-wire, 60-amp, 250-Volt,
UL-approved. Color blue,
IEC 309-1, IEC 309-1,
grounded at 9:00 o'clock.

a

Mennekes ME 460R9 3
phase,
4-wire, 60-amp, 250-Volt,
UL-approved. Color blue,
IEC 309-1, IEC 309-1,
grounded at 9:00 o'clock.

b

A5800A Option 007 Five conductors, 10-

AWG (6 mm

2

),

450/475-Volt, 32-
Amp,
European wire
cordage, GN/YW
ground wire.

Mennekes ME
532P6-14 3-phase,
5-wire, 32-Amp,
450/475-volt, VDE-
certified, color red,
IEC 309-1, IEC 309-
2, grounded at 6:00
o'clock.

Mennekes ME 532C6 16 3-
phase, 5-wire, 32-Amp,
450/475-Volt, VDE-
certified, color red, IEC
309-1, IEC 309-2,
grounded at 6:00 o'clock.

c

Mennekes ME532R6 1276
3-phase, 5-wire, 32-Amp,
450/475-Volt, VDE-
certified, color red, IEC
309-1, IEC 309-2,
grounded at 6:00 o'clock.

b

a. In line connector is available from HP by purchasing A6440A, Option 401.
b. Panel mount receptacles must be purchased by the customer from a local Mennekes supplier.
c. In line connector is available from HP by purchasing A6440A, Option 501.

NOTE:

NOTE:

NOTE:

NOTE: A qualified electrician must wire the PDCA in line connector to site power using copper wire and in compliance
with all local codes.

Input Requirements

Input Requirements

Input Requirements

Input Requirements
Reference the Site Preparation Guide for detailed power configuration requirements.

Requirements

Requirements

Requirements

Requirements

Value

Value

Value

Value

Conditions/Comments

Conditions/Comments

Conditions/Comments

Conditions/Comments

Nominal Input Voltage (VAC rms)

200/208/220/230/240

Input Voltage Range (VAC rms)

200-240

Auto selecting. Measure at input
terminals

Frequency Range (Hz)

50/60

Number of Phases

3

3-phase 5-wire with power cord;
3-phase 4-wire with power cord

Maximum Input Current (A rms), 3-
Phase 5-wire

20

3-phase source with a source voltage of
220 VAC measured phase to neutral

Maximum Input Current (A rms), 3-
Phase 4-wire

40

3-phase source with a source voltage of
either 208 VAC or 230 VAC measured
phase to phase

Maximum Inrush Current (A peak)

90

Circuit Breaker Rating (A),
3-Phase 5-wire

25 A

Per phase

Circuit Breaker Rating (A),
3-Phase 4-wire

45 A

Per phase

Power Factor Correction

0.95 minimum

Ground Leakage Current (mA)

>3.5 mA, with 6 BPSs installed

Warning label applied to the PDCA at
the AC Mains input

Cooling Requirements

Cooling Requirements

Cooling Requirements

Cooling Requirements

The cooling system in Superdome was designed to maintain reliable operation of the system in the specified
environment. In addition, the system is designed to provide redundant cooling (i.e. N+1 fans and blowers) that
allows all of the cooling components to be "hot swapped."
Superdome was designed to operate in all data center environments with any traditional room cooling scheme (i.e.
raised floor environments) but in some cases where data centers have previously installed high power density systems,

QuickSpecs

HP Integrity Superdome Servers: 16-way, 32-way,

HP Integrity Superdome Servers: 16-way, 32-way,

HP Integrity Superdome Servers: 16-way, 32-way,

HP Integrity Superdome Servers: 16-way, 32-way,

and 64-way

and 64-way

and 64-way

and 64-way

Configuration

DA - 11717 Worldwide — Version 1 — June 30, 2003

Page 17