beautypg.com

Installation options, Metal heat circulating masonry – Hearth and Home Technologies 3100-I User Manual

Page 9

background image

Page 9

September 1, 2008

3100-I ACT WOOD INSERT

R

250-638D

MASONRY FIREPLACE

USING DIRECT-CONNECT METHOD

Refer to: Clearances to Combustibles on page 5, Canadian Installation requirements on page 11,

Hearth Requirements on page 5 and Zero Clearance Adjustable Support Kit on page 14.

Figure 9A - Installation Into Masonry Fireplace

Direct Connect

Seal Option

Minimum Starter

Pipe Option

Full Listed

Liner Option

Masonry Chimney

Flue Tile

Mantel

Air-tight Face Seal

Damper Area

SEAL DAMPER AREA OR FACE SEAL

INSTALLATION OPTIONS

The Quadra-Fire 3100-I ACT Insert conforms with the UL

Standard for Safety 1482 and ULC S628 (Canada) in all

respects, and is approved to UL & ULC safety standards

for installation and use within a fireplace with a masonry

chimney in accordance with NFPA No. 211, with or without

a direct flue collar connection. A starter pipe is required to

reach to the bottom of the existing flue.

1. Secure the fireplace damper in the open position. If this

cannot be accomplished, it will be necessary to remove the

damper.

. Seal the damper area around the chimney liner with a

high temperature sealant.

3. The chimney should be examined for cracks, loose mortar,

and other signs of deterioration and blockage. The insert

should not be installed until it is determined that the chim-

ney is safe for use. Since an oversized flue contributes to

the accumulation of creosote, the size of the flue should be

checked to determine that it is not too large for the insert.

The chimney should also be checked to ensure it meets the

minimum standard of the National Fire Protection Associa-

tion (NFPA) Standard 211. The following bullets list the more

critical requirements for a properly constructed chimney:

The masonry wall of the chimney, if brick or modular

block, must be a minimum of 4 inches (102mm) nominal

thickness. A chimney of rubble stone must be at least 12

inches (305mm) thick

The chimney must have a fire clay flue liner (or equiva-

lent) with a minimum thickness of 5/8” (16mm) and must be

installed with refractory mortar. An equivalent liner must be

a listed chimney liner system or other approved material.

A chimney inside the house must have at least inches

(51mm) of clearance to the combustible structure. A chim-

ney outside the house must have at least 1 inch (25mm)

clearance to the combustible structure. Non-combustible fire

stops must be installed at the spaces where the chimney

passes through floors and/or ceiling

(See Figure 8A and 8B

on page 8).

NOTE: In Canada, a full reline is required.

METAL HEAT CIRCULATING MASONRY

The Quadra-Fire 3100-I Insert conforms with the safety stan-
dard UL-1482 and ULC S628 (Canada) in all respects and is
approved to UL & ULC safety standards for installation and
use within a fireplace with masonry chimney, in accordance
with NFPA No. 211, with or without a direct flue collar con-
nection. A starter pipe is required into existing chimney.

Figure 9B

-

Installation Into Metal Heat Circulating

Showing Use Of Starter Pipe

Listed Liner

Mantel

SEAL DAMPER AREA OR FACE SEAL

This manual is related to the following products: