SPECIFICATIONS

Gas Supply

Installation must comply with local codes or, in the absence
of local codes, with the National Fuel Gas Code.

Locate the gas supply within the shaded area shown in the
illustrations on pages 7–8.

The outdoor grill is equipped for use with natural or liquid
propane (LP) gas. It is design certified by the Canadian
Standards Association (CSA) for natural or LP gases. The
product rating plate has information on the type of gas that
should be used. For rating plate location, refer to the illustra-
tion below. If this information does not agree with the type
of gas available, check with the local gas supplier.

GAS REQUIREMENTS

NATURAL GAS

WC

Supply Pressure

5"

(12.5 mb)

Min Line Pressure

7"

(17.5 mb)

Max Regulator Pressure

14"

(34.9 mb)

, .5 psi

(3.5 kPa)

LP GAS

WC

Supply Pressure

10"

(25 mb)

Min Line Pressure

11"

(27.4 mb)

Max Regulator Pressure

14"

(34.9 mb)

, .5 psi

(3.5 kPa)

The outdoor grill must be connected to a regulated gas
supply. The supply line must be equipped with an approved
external gas shut-off valve located near the grill in an acces-
sible location. Do not block access to the shut-off valve.
Refer to the illustration below.

A gas supply line of

3

/

4

"

(19)

rigid pipe must be provided to

the outdoor grill or module. If local codes permit, a certified,
3'

(.9 m)

long,

1

/

2

"

(13)

or

3

/

4

"

(19)

ID flexible metal appliance

connector is recommended to connect the units

1

/

2

" NPT

female inlet to the gas supply line. Pipe joint compounds,
suitable for use with natural or LP gas should be used.

The appliance and its shut-off valve must be disconnected
from the gas supply piping system during any pressure
testing of the system at test pressures in excess of .5 psi

(3.5 kPa)

. The appliance must be isolated from the gas

supply piping system by closing its individual manual shut-
off valve during any pressure testing of the system at test
pressures equal to or less than .5 psi

(3.5 kPa)

.


Outdoor gas grill.


Outdoor module.

RATING PLATE

RATING PLATE

SHUT-OFF VALVE

OPEN POSITION

GAS SUPPLY

TO APPLIANCE


Gas shut-off valve.