Mnet error and status data, Mnet client error/status data – ProSoft Technology 5201-MNET-ASCII User Manual
Page 50
Diagnostics and Troubleshooting
MNET ♦ ProLinx Gateway
Driver Manual
Modbus TCP/IP Interface Module
Page 50 of 78
ProSoft Technology, Inc.
September 1, 2010
3.3
MNET Error and Status Data
The following topics list the register addresses that contain error and status data.
Use the Database View option from the ProLinx Main Menu to view the contents
of each register. The ProLinx Reference Guide provides the information on using
this option.
3.3.1 MNET Client Error/Status Data
The Client connection Error and Status Data areas are discussed in this section.
The error/status data table is located at the virtual addresses 6000 through 6009.
This data will be available through the Configuration/Debug Port or through the
Server driver, if requested by a remote Client.
The data area is initialized with zeros whenever the gateway is initialized. This
occurs during a cold-start (power-on), reset (reset push-button pressed) or a
warm-boot operation (commanded from the Diagnostics menu or immediately
after a new configuration has been downloaded).
Internal Database Address
Description
6000
Command Request Count (total Client commands sent)
6001
Command Response Count (total command responses received)
6002
Command Error Count
6003
Number of Request Packets
6004
Number of Response Packets
6005
Errors Sent
6006
Errors Received
6007
Configuration Error Word
6008
Current Error
6009
Last Error
Registers 6000 through 6006 are counters and are shown as 16-bit signed
integer values in the range of -32768 to +32767. When a count exceeds +32767,
it will automatically rollover to -32768 and become less negative (increment) with
each additional count.
Register 6007, the MNET Configuration Error Word, is a bit-mapped value. Not
all bits are used; some are reserved for future use. The bit-map indicates the
following errors if specific bits are set to 1. Note that, since this is a bit map, if
multiple errors are present, the value displayed with be the sum of the values
shown in the chart for all of the bits set to 1.
Bit
Decimal Value
Description
0
0001
Reserved
1
0002
Reserved
2
0004
Reserved
3
0008
Reserved
4
0016
Invalid Retry Count (0 to 10)
5
0032
Invalid Float Flag (Y or N)
- 5201-MNET-DFCM 5208-MNET-HART 5303-MBP-MNET 5204SE-MNET-PDPMV1 5202-MNET-ADM4 5201-MNET-BACNET 5210-MNET-RIO 5228-MNET-HART 5207-MNET-HART 5205-MNET-PDPS 5204-MNET-PDPMV1 5201-MNET-DH485 5201-MNET-104S 5201-MNET-EGD 5201-MNET-DFNT 5201-MNET-DNPSNET 5201-MNET-103M 5201-MNET-101S 5201-MNET-DNPS 5201-MNET-DNPM 5202-MNET-DFCM4 5202-MNET-ASCII4