Mnet client 0, Minimum command delay, Response timeout – ProSoft Technology 5201-MNET-ASCII User Manual
Page 22: Retry count
![background image](https://www.manualsdir.com/files/866211/content/doc022.png)
Modbus TCP/IP Protocol Configuration
MNET ♦ ProLinx Gateway
Driver Manual
Modbus TCP/IP Interface Module
Page 22 of 78
ProSoft Technology, Inc.
September 1, 2010
2.4
[MNET CLIENT 0]
The [MNET CLIENT 0] section of the CFG file specifies the parameters for the
client to be emulated on the gateway. The command list for the client is entered
in a separate section.
2.4.1 Minimum Command Delay
0 to 32767
This parameter specifies the number of milliseconds to wait between the initial
issuance of a command. This parameter can be used to delay all commands sent
to slaves to avoid "flooding" commands on the network. This parameter does not
affect retries of a command as they will be issued when failure is recognized.
2.4.2 Response Timeout
0 to 65535 milliseconds
This is the time in milliseconds that a Client will wait before re-transmitting a
command if no response is received from the addressed server. The value to use
depends upon the type of communication network used, and the expected
response time of the slowest device on the network.
2.4.3 Retry Count
0 to 10
This parameter specifies the number of times a command will be retried if it fails.
- 5201-MNET-DFCM 5208-MNET-HART 5303-MBP-MNET 5204SE-MNET-PDPMV1 5202-MNET-ADM4 5201-MNET-BACNET 5210-MNET-RIO 5228-MNET-HART 5207-MNET-HART 5205-MNET-PDPS 5204-MNET-PDPMV1 5201-MNET-DH485 5201-MNET-104S 5201-MNET-EGD 5201-MNET-DFNT 5201-MNET-DNPSNET 5201-MNET-103M 5201-MNET-101S 5201-MNET-DNPS 5201-MNET-DNPM 5202-MNET-DFCM4 5202-MNET-ASCII4