ProSoft Technology MVI46-DFCM User Manual
Page 86

MVI46-DFCM ♦ SLC Platform
Reference
DF1 Communication Module
Page 86 of 103
ProSoft Technology, Inc.
October 20, 2008
Column
Parameter
Description
Parameter
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 151
Word Range Read Command.
8
File String
PLC-5 address as specified as an ASCII string. For
example, N10:300.
P1
9 to 11
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function reads one or more words of data from a PLC data table. This
function should work on the following devices: PLC-5.
Function Code #152 - Read-Modify-Write (PLC-5 Command) (ASCII Address)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled, 1=Continuous and 2=Conditional.
2
Virtual Database Address
This parameter defines the database address for the
data to be associated with the command. The first
database register is used as the AND mask for the
command, and the second is used for the OR mask.
Values in the AND mask have the following definitions:
0=Reset and 1=Leave the Same. Values in the OR
mask have the following definitions: 0=Leave the Same
and 1=Set.
3
Poll Interval
Minimum time in tenths of a second to wait before
polling with this command.
4
Count
Number of data word values to be considered by the
function.
5
Swap Type Code
Swap type code for command: Always zero (0).
6
Node Address
Address of unit to reach on the data highway.
7
Function Code = 152
Read-Modify-Write Command.
8
File String
PLC-5 address as specified as an ASCII string. For
example, N10:300.
P1
9 to 11
Not Used
These fields are not used by the command. Values
entered in these columns will be ignored.
P2 to P4
This function writes one or more words of data to a PLC data table. This function
should work on the following devices: PLC-5. The command constructed
contains an AND mask and an OR mask. Values in the AND mask have the
following definitions: 0=Reset and 1=Leave the Same. Values in the OR mask
have the following definitions: 0=Leave the Same and 1=Set. The module is
responsible for setting the mask values to correctly construct the message from
the virtual database values.
Function Code #501 - Protected Typed Logical Read (Two Address Fields)
Column
Parameter
Description
Parameter
1
Enable/Type Word
0=Disabled and 1=Continuous.
2
Virtual Database Address
This parameter defines the database address of the first
data point to be associated with the command.
3
Poll Interval
Minimum number of seconds to wait before polling with
this command.
4
Count
Number of data word values to be considered by the
function.