ProSoft Technology MVI46-DFCM User Manual
Page 27

Installing and Configuring the Module
MVI46-DFCM ♦ SLC Platform
DF1 Communication Module
ProSoft Technology, Inc.
Page 27 of 103
October 20, 2008
Database in SLC
Database in MVI46-DFCM
File
M0 Offset
File
Register Content
Description
N10:35
36
N32:44
5044
Termination
Type
This parameter specifies the error
checking for all DF1 messages.
0=BCC, 1=CRC
N10:36
37
N32:45
5045
Baud Rate
This is the baud rate to be used
on the port. Enter the baud rate
as a value
Baud
Rate
Parameter Value
110
110
150
150
300
300
600
600
1200
12 or 1200
2400
24 or 2400
4800
48 or 4800
9600
96 or 9600
14,400
14, 114 or 14400
19,200
19, 192 or 19200
28,800
28, 288 or 28800
38,400
38, 384 or 38400
57,600
57 or 576
115,200 115 or 1152
N10:37
38
N32:46
5046
Parity
This is the Parity code to be used
for the port. The coded values are
as follows: 0=None, 1=Odd,
2=Even, 3=Mark and 4=Space.
N10:38
39
N32:47
5047
Data Bits
This parameter sets the number
of data bits for each word used by
the protocol. Valid value in the
range of 5 to 8.
N10:39
40
N32:48
5048
Stop Bits
This parameter sets the number
of stop bits to be used with each
data value sent. Valid value of 1
or 2.
N10:40
41
N32:49
5049
Minimum
Response
Delay
This parameter sets the number
of milliseconds to wait before a
response message is sent out of
the port. This parameter is
required when interfacing to a
slow responding device. Valid
value in the range of 0 to 65535.
N10:41
42
N32:50
5050
RTS On
Delay
This parameter sets the number
of milliseconds to delay after RTS
is asserted before the data will be
transmitted. Valid value in the
range of 0 to 65535.
N10:42
43
N32:51
5051
RTS Off
Delay
This parameter sets the number
of milliseconds to delay after the
last byte of data is sent before the
RTS modem signal will be set
low. Valid value in the range of 0
to 65535.