1 backplane configuration – ProSoft Technology MVI46-DFCM User Manual
Page 22

MVI46-DFCM ♦ SLC Platform
Installing and Configuring the Module
DF1 Communication Module
Page 22 of 103
ProSoft Technology, Inc.
October 20, 2008
Register Range
File Start
File End
Content
Size
0 to 4999
N7:0
N31:199
User Data
5000
5000 to 5009
N32:0
N32:9
Backplane Configuration
10
5010 to 5039
N32:10
N32:39
Port 1 Setup
30
5040 to 5069
N32:40
N32:69
Port 2 Setup
30
5070 to 5199
N32:70
N32:199
Reserved
130
5200 to 6399
N33:0
N38:199
Port 1 Commands
1200
6400 to 7599
N39:0
N44:199
Port 2 Commands
1200
7600 to 7700
N45:0
N45:199
Misc. Status Data
200
7800 to 7999
N46:0
N46:199
Command Control
200
8000 to 9999
N47:0
N56:199
Reserved
2000
The user data areas hold data collected from other nodes on the network (master
read commands) or data received from the processor. Additionally, this data area
is used as a data source for the processor (read blocks) or other nodes on the
network (write commands).
2.2.1 Backplane
Configuration
Database in SLC
Database in MVI46-DFCM
File
M0 Offset
File
Register
Content
Description
N10:0
1
N32:0
5000
Write Start Reg Not used in this version of the software
N10:1
2
N32:1
5001
Write Reg
Count
Not used in this version of the software
N10:2
3
N32:2
5002
Read Start Reg Not used in this version of the software
N10:3
4
N32:3
5003
Read Reg
Count
Not used in this version of the software
N10:4
5
N32:4
5004
Backplane Fail This parameter specifies the number of
successive transfer errors that must
occur before the communication ports
are shut down. If the parameter is set to
0, the communication ports will continue
to operate under all conditions. If the
value is set larger than 0 (1 to 65535),
communications will cease if the
specified number of failures occur.
N10:5
6
N32:5
5005
Error Status
Pointer
This parameter specifies the register
location in the module's database where
module status data will be stored. If a
value less than 0 is entered, the data will
not be stored in the database. If the
value specified is in the range of 0 to
4940, the data will be placed in the user
data area.
N/A
N/A
N32:6
5006
Spare
Not used
N/A
N/A
N32:7
5007
Spare
Not used
N/A
N/A
N32:8
5008
Spare
Not used
N/A
N/A
N32:9
5009
Spare
Not used