ProSoft Technology MVI46-DFCM User Manual
Page 25

Installing and Configuring the Module
MVI46-DFCM ♦ SLC Platform
DF1 Communication Module
ProSoft Technology, Inc.
Page 25 of 103
October 20, 2008
Database in SLC
Database in MVI46-DFCM
File
M0 Offset
File
Register
Content
Description
N10:21
22
N32:25
5025
Minimum
Command
Delay
This parameter specifies the
number of milliseconds to wait
between the initial issuance of a
command. This parameter can be
used to delay all commands sent
to slaves to avoid "flooding"
commands on the network. This
parameter does not affect retries
of a command as they will be
issued when failure is recognized.
Valid value in the range of 0 to
65535.
N10:22
23
N32:26
5026
Command
Error Pointer
This parameter sets the address
in the internal DF1 database
where the command error data
will be placed. If the value is set
to -1, the data will not be
transferred to the database. Valid
value of 0 to 4999.
N10:23
24
N32:27
5027
Response
Timeout
This parameter represents the
message response timeout
period in 1-ms increments. This is
the time that a port configured as
a master will wait before re-
transmitting a command if no
response is received from the
addressed slave. The value is set
depending upon the
communication network used and
the expected response time of
the slowest device on the
network.
N10:24
25
N32:28
5028
Retry Count This parameter specifies the
number of times a command will
be retried if it fails. Valid value in
the range of 0 to 10.
N10:25
26
N32:29
5029
Error Delay
Count
This parameter specifies the
number of polls to be skipped on
the slave before trying to re-
establish communications. After
the slave fails to respond, the
master will skip commands to be
sent to the slave the number of
times entered in this parameter.
Valid value in the range of 0 to
65535.
N10:26
27
N32:30
5030
Slave List
Pointer
This parameter specifies the
starting address in the virtual
database where the 256 slave
status values will be written. If the
parameter is set to -1, the slave
data will not be placed in the
database. Valid value in the
range of -1 to 4743.
N10:27
28
N32:31
5031
Slave List
Frequency
Not used in this version of the
software