ProSoft Technology MVI46-DFCM User Manual
Page 54

MVI46-DFCM ♦ SLC Platform
Reference
DF1 Communication Module
Page 54 of 103
ProSoft Technology, Inc.
October 20, 2008
5.1.2 Hardware
Specifications
Specification Description
Backplane Current Load
800 ma @ 5V (from backplane)
Operating Temperature
0 to 60°C (32 to 140°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Shock
30g operational, 50g non-operational
Relative Humidity
5% to 95% (non-condensing)
Vibration
5 g from 10150 Hz
Processor
Compatible with Rockwell Automation SLC 5/02 M0/M1
capable processors or newer
LED indicators
Module status, Backplane transfer status, Application status,
Serial activity and error LED status
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
Configuration Connector
RJ45 RS-232 Connector (RJ45 to DB-9 cable shipped with
unit)
Application Ports
Application Serial port (PRT1,
PRT2) (Serial Modules)
Two RJ45 RS-232/422/485 Application ports
5.1.3 Functional
Specifications
DF1 ports
Full and half duplex modes supported
CRC and BCC error checking
Full hardware handshaking control
User-definable module memory usage, supporting the storage and transfer of
up to 5000 registers to/from the control processor
Up to 125 word read and write command lengths supported
Floating point data movement supported
DF1 Master Protocol Specifications
The ports on the DF1 module can be individually configured as Master ports.
When configured in master mode, the DFCM module is capable of reading and
writing data to remote DF1 devices, enabling the SLC platform to act as a
SCADA sub-master.
Command List: Up to 100 commands per Master port, each fully-configurable
for function, slave address, register to/from addressing and word/byte count
Status Data: Error codes available on an individual command basis. In
addition, a slave status list is maintained per active master port
Polling of Command List: User-configurable polling of commands, including
disabled, continuous, and on change of data (write only)