MVI71-GEC ♦ PLC 5 Platform
Reference
Generic ASCII Ethernet Communication Module
User Manual
ProSoft Technology, Inc.
Page 47 of 86
May 11, 2011
5.1.3 Functional Specifications
Five Servers and Clients to receive and/or transmit data
10/100 Base-T Ethernet-compatible interface
Configurable parameters
o
Service port number
o
Connection timeout
o
Close type
Simple ladder logic operation
Setup and monitoring through RS-Logix 5 software and user-constructed
configuration file (GEC.CFG)
PLC backplane interface via I/O access
Each Server monitors
o
State
o
IP and port number of connected Client
o
Error codes
Each Client monitors
o
State
o
IP and port number of connected Server
o
Message related parameters
ASCII character strings up to 2048 characters in length supported
Full hardware handshaking control, providing radio, modem, and multi-drop
support
User-definable module memory usage, supporting the storage and transfer of
up to 4000 bytes to/from the control processor
Module error and status conditions returned to processor for diagnostic
purposes
o
Module status
o
Port error status word (bit mapped)
o
Port receive state
o
Port receive character count
o
Port receive block count
o
Port transmit state
o
Port transmit character count
o
Port transmit block count