ProSoft Technology MVI71-GEC User Manual
Page 46

Reference
MVI71-GEC ♦ PLC 5 Platform
User Manual
Generic ASCII Ethernet Communication Module
Page 46 of 86
ProSoft Technology, Inc.
May 11, 2011
5.1
Product Specifications
The MVI71 Generic ASCII Ethernet Interface module is designed to allow PLC
processors to interface easily with ASCII devices using the TCP/IP protocol.
Compatible devices may be either ASCII instruments with built-in Ethernet or
Ethernet connection via a thin server to the existing ASCII device.
Five servers and Clients are present on the module permitting both the reception
and transmission of data between the Rockwell Automation processor and attached
devices.
The MVI71-GEC module is a powerful communication interface for PLC processors.
Developed under license from Rockwell Automation, the module incorporates
proprietary backplane technology that enables powerful data access between the
module and the PLC processor.
5.1.1 General Specifications
Single Slot - 1771 backplane compatible
The module is recognized as an Input/Output module and has access to
processor memory for data transfer between processor and module
Ladder Logic is used for data transfer between module and processor.
Sample ladder file included.
5.1.2 Hardware Specifications
Specification
Description
Form Factor
Single Slot 1771 chassis compatible
BTR/BTW data transfer
Local or remote rack
Backplane current load
800 mA @ 5 V
Operating temperature
32 to 140°F (0°C to 60°C)
Storage temperature
-40°F to 185°F (-40°C to 85°C)
Shock
30g operational
50g non-operational
Vibration
5 g from 10150 Hz
Relative Humidity
5% to 95%, RH with no condensation
LED Indicators
Module status
Backplane transfer status
Application status
Serial activity and error LED status
Configuration Serial Port (CFG) DB-9M PC compatible
RS-232
Hardware handshaking
Ethernet Port (Ethernet
modules)
RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz
for 60 s, applied as specified in section 5.3.2 of IEC
60950: 1991
Ethernet Broadcast Storm Resiliency = less than or
equal to 5000 [ARP] frames-per-second and less
than or equal to 5 minutes duration