ProSoft Technology MVI56-BSAPS User Manual
Page 71
Reference MVI56-BSAPS
♦ ControlLogix Platform
Bristol Babcock Serial Slave Module
ProSoft Technology, Inc.
Page 71 of 83
September 22, 2008
Offset Content
Description
220
Number of responses:
Port 2
Contains the total number of messages received on the
port.
221
Number of errors sent:
Port 2
Contains the total number of message errors sent out
the port.
222
Number of errors received:
Port 2
Contains the total number of message errors received
on the port.
223
Backplane Transfer Writes Contains the total number of write blocks transferred
from the processor to the module.
224
Backplane Transfer Reads Contains the total number of read blocks transferred
from the module to the processor.
225
Backplane Blocks Parsed
226
Backplane Transfer Errors Contains the total number of block errors recognized by
the module.
227
Current Error: Port 1
For a slave port, this field contains the value of the
current error code returned. For a master port, this field
contains the index of the currently executing command.
228
Last Error: Port 1
For a slave port, this field contains the value of the last
error code returned. For a master port, this field contains
the index of the command with the error.
229
Current Error: Port 2
For a slave port, this field contains the value of the
current error code returned. For a master port, this field
contains the index of the current executing command.
230
Last Error: Port 2
For a slave port, this field contains the value of the last
error code returned. For a master port, this field contains
the index of the command with an error.
A data file should be allocated in the ladder logic to hold this block of data. The
size of the block of data is 35 words.