Module, Module type, Module name – ProSoft Technology MVI56-BSAPS User Manual
Page 29: Backplane 56, Read register start, Read register count, Write register start, Backplane fail count

Module Configuration
MVI56-BSAPS ♦ ControlLogix Platform
Bristol Babcock Serial Slave Module
ProSoft Technology, Inc.
Page 29 of 83
September 22, 2008
2.3 [Module]
This section is used to define the configuration for the Module level data.
2.3.1 Module
Type
The part number for the module, for example MVI56-BSAPS
2.3.2 Module
Name
0 to 80 characters
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.
2.4 [Backplane
56]
2.4.1 Read Register Start
Range 0 to 3999
This parameter specifies the starting register in the module where data will be
transferred from the module to the processor. Valid range for this parameter is 0
to 3999.
2.4.2 Read Register Count
0 to 4000
The Read Register Count parameter defines the size of the module's input
database, up to a maximum value of 4000 words.
2.4.3 Write Register Start
0 to 3999
This parameter specifies the starting register in the module where the data will be
transferred from the processor to the module.
2.4.4 Read Register Count
0 to 4000
The Read Register Count parameter defines the size of the module's input
database, up to a maximum value of 4000 words.
2.4.5 Backplane Fail Count
0 to 65535
This parameter specifies the number of consecutive backplane transfer failures
that can occur before communications should be halted.