Attribute name, Signal descriptor, Bsap port x – ProSoft Technology MVI56-BSAPS User Manual
Page 32: Enable, Baud rate, Parity, Data bits, Stop bits, Bsap, Port x
MVI56-BSAPS ♦ ControlLogix Platform
Module Configuration
Bristol Babcock Serial Slave Module
Page 32 of 83
ProSoft Technology, Inc.
September 22, 2008
2.6.12 Attribute Name
Max char of Attribute Name = 4
2.6.13 Signal Descriptor
Max char of Signal Descriptor = 64
2.7
[BSAP Port x]
This section is used to define the port configuration for the BSAPS device
simulated on network port.
2.7.1 Enable
Enable: Yes #No=Port Disabled,Yes=Port Enabled
This parameter defines if the port will be used. If the parameter is set to No, the
port is disabled. A value of Yes enables the port.
2.7.2 Baud
Rate
Baudrate: 1200 #Baudrate for port (110 to 115.2K)
This is the baud rate to be used for the port. Enter the baud rate as a value. Baud
rate entries are 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 28800,
57600, 115200.
2.7.3 Parity
None, Odd, Even, Mark, Space
Parity is a simple error checking algorithm used in serial communication. This
parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.
2.7.4 Data
Bits
5, 6, 7 or 8
This parameter sets the number of data bits for each word used by the protocol.
2.7.5 Stop
Bits
1 or 2
Stop bits signal the end of a character in the data stream. For most applications,
use one stop bit. For slower devices that require more time to resynchronize, use
two stop bits.
All devices communicating through this port must use the same number of stop
bits.