4.2.3 Termination of Received Data
When data is received on either of the application ports, you must define in the
configuration when this data will be transferred to the ControlLogix processor.
Within the module, this is known as the termination type for port. When the
termination condition is met, the data will be sent from the port’s receive buffer
(data area of 4096 bytes) to the processor using the input image. This
termination type is set using a bit-mapped value, entered into the
GSC.CONFIG.P
ORT
X.T
YPE
field of the configuration controller tags.
Termination Mode Selection Chart
0 = No Bits
Set
1 = Bit 0 Set
2 = Bit 1 Set
4 = Bit 2 Set
8 = Bit 3 Set
Decimal
Value of
Bits
Selected
(S)
Streaming
Mode
Selected
(T)
Terminating
Characters
Selected
(M)
Message
Timeout
Selected
(D)
Intercharacter
Delay
Selected
(P)
Packet Length
Selected
Port Types
Selected by
Bitmap
0
0
S
1
1
T
2
2
M