Diagnostics and Troubleshooting
MVI56E-GSC ♦ CompactLogix or MicroLogix Platform
User Manual
Enhanced Generic ASCII Serial Communication Module
Page 72 of 140
ProSoft Technology, Inc.
May 9, 2014
Initialization Messages
Message
Meaning
"Boot"
Module is initializing its operating system
"Waiting for Processor
Connection..."
Module is not able to establish a backplane connection with
the ControlLogix PAC. Possible causes:
Ladder logic or AOI is not loaded on processor
Module is located in a different slot than the one
configured in the ladder logic/AOI
Module I/O properties are invalid
Processor is not in RUN or REM RUN mode
"INIT"
Module is beginning its firmware initialization
"Ladder Logic Configuration
Required"
Module is waiting for valid module configuration data from
ladder logic. Check that module configuration parameters are
set to valid values in the ladder logic controller tags
"UPDATING"
Module is performing a firmware update, initiated from the
web page.
"STOP"
Module firmware is stopping after receiving a "Cold Boot"
request, which forces an automatic re-start, same as from
power-up
"MVI-56E-GSC
Config:
After power up and every reconfiguration reboot, the module
will display the configuration of both ports. This message will
scroll through once and not be repeated until the next reboot.
The message contains:
STREAM - Streaming
TERM - Terminating Characters
DELAY - Intercharacter Delay
PACKET - Packet Length
MSGTO - Message Timeout
4800 / 2400 / 1200 / 600 / 300
Initialization Error Messages
During initialization, if the module detects a unrecoverable fault that will prevent
communication, an error message will be displayed. If any of these errors persist
after repeated reboot attempts, contact ProSoft Technology Technical Support
for further assistance.
Message
Meaning
"E003"
Startup sequence failed, module failed to initialize
"E005"
Displayed during startup if there is an error opening
application serial Port 1(P1)