ProSoft Technology MVI69-103M User Manual
Page 72

MVI69-103M ♦ CompactLogix or MicroLogix Platform
Reference
IEC 60870-5-103 Master Communication Module
Page 72 of 131
ProSoft Technology, Inc.
November 3, 2008
5.1.2 Hardware
Specifications
Specification Description
Dimensions
Standard 1769 Single-slot module
Current Load
800 mA max@ 5 VDC
Power supply distance rating of 2
Operating Temp.
0 to 60°C (32 to 140°F)
Storage Temp.
-40 to 85°C (-40 to 185°F)
Relative Humidity
5% to 95% (non-condensing)
LED Indicators
Power and Module Status
Application Status
Serial Port Activity
Error Status
CFG Port (CFG)
RJ45 (DB-9F with supplied cable)
RS-232 only
No hardware handshaking
App Ports (P1,P2) (Serial modules)
RJ45 (DB-9F with supplied cable)
RS-232, RS-422 and RS-485 modes supported.
Both ports operate as individual IEC 60870-3-103
controlling units (masters)
500V Optical isolation from backplane
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable
5.1.3 Functional
Specifications
The MVI69-103M module supports the IEC 60870-5-103 protocol to the following
specifications:
The IEC 60870-5-103 communication driver is built in accordance to the
approved IEC specification
User-definable module memory usage
The module has two independent master ports, each configurable via a
simple configuration file
Supports up to 16 sessions (controlled devices) between the two ports
Supports up to three sectors (separate databases) for each session, with
individual database definition for each sector
Total of 1000 user configurable commands to control data transfer to/from
devices (controlled devices)
Supports clock synchronization from/to the processor
Event data received from the Control Devices updates the module database
(Date and Time stamping is not stored or used by module)
Class 1 and Class 2 delay parameters are configurable for each session
An IEC Interoperability Document for the module is available from the web
site, which fully documents data types supported by the module