ProSoft Technology MVI69-103M User Manual
Page 106
![background image](https://www.manualsdir.com/files/866101/content/doc106.png)
MVI69-103M ♦ CompactLogix or MicroLogix Platform
Reference
IEC 60870-5-103 Master Communication Module
Page 106 of 131
ProSoft Technology, Inc.
November 3, 2008
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
29 auxiliary
input
3
X 1 X X X X
30 auxiliary
input
4
X 1 X X X X
Supervision indications
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
32
measured supervision I
X
1
X
X
33
measured supervision V
X
1
X
X
35
phase sequence supervision
X
1
X
X
36
trip
circuit
supervision
X 1 X X X X
37
l>>back-up operation
X
1
X
38
VT fuse failure
X
1
X
X
39
teleprotection
disturbed
X 1 X X X
46
group
warning
X 1 X X X X
47
group
alarm
X 1 X X X X
Earth fault indications
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
48
earth fault L
1
X
1
X
X
49
earth fault L
2
X
1
X
X
50
earth fault L
3
X
1
X
X
51
earth fault forward (that is, line)
X
1
X
X
52
earth fault reverse (that is, busbar)
X
1
X
X
Fault indications
Fun
128 160 176 192 254 255
Inf Description
GI Type
t(z) l>>
∆l
T
∆l
L
GEN GLB
64 start/pick-up
L
1
X 2 X X X
65 start/pick-up
L
2
X 2 X X X
66 start/pick-up
L
3
X 2 X X X
67
start/pick-up
N
X 2 X X X
68
general
trip
2 X X X X
69 trip
L
1
2 X X X X