ProSoft Technology MVI69-103M User Manual
Page 26
![background image](https://www.manualsdir.com/files/866101/content/doc026.png)
MVI69-103M ♦ CompactLogix or MicroLogix Platform
Configuring the MVI69-103M Module
IEC 60870-5-103 Master Communication Module
Page 26 of 131
ProSoft Technology, Inc.
November 3, 2008
2.5.3 Data
Link
Address
0 to 254
This parameter uniquely defines the data link address for this unit on the
communication channel. The ranges of values are from 0 to 254. Address 255 is
the broadcast address.
2.5.4 Failure
Delay
0 to 2000
This parameter sets the minimum number of seconds to delay before polling this
session when it is not online. This parameter is only used in unbalanced mode.
2.5.5 Confirm
Timeout
0 to 2^32-1
This parameter sets the number of milliseconds to wait for a confirm response
from the controlled device.
2.5.6 Retry
Count
0 to 255
This parameter sets the number of retries to be performed on the controlled
device when a communication occurs.
2.5.7 C1/C2 Poll Count Pend
0 to 65535
This parameter sets the maximum number of class 1 and class 2 polls performed
on this session before trying the next session. This parameter prevents a session
from monopolizing the communication port.
2.5.8 Class 1 Polls
0 to 100
This parameter sets the maximum number of class 1 polls performed on this
session before switching to another session. This parameter prevents a session
from monopolizing the communication port.
2.5.9 Class 1 Pend Delay
0 to 2^32-1
This parameter sets the minimum number of milliseconds to delay between class
1 polls for pending data.