ProSoft Technology MVI69-103M User Manual
Page 50

MVI69-103M ♦ CompactLogix or MicroLogix Platform
Ladder Logic
IEC 60870-5-103 Master Communication Module
Page 50 of 131
ProSoft Technology, Inc.
November 3, 2008
4 Enter the values shown in the following illustration to define the module
correctly for the MicroLogix processor, and then click OK to save your
configuration.
The input words and output words parameter will depend on the Block
Transfer Size parameter you specify in the configuration file. Use the values
from the following table.
Block Transfer Size
Input Words
Output Words
60 62
61
120 122
121
240 242
241
5 Click Next to continue.
6 After completing the module setup, the I/O configuration dialog box will
display the module's presence.
The last step is to add the ladder logic. If you are using the example ladder logic,
adjust the ladder to fit your application. Refer to the example Ladder Logic
section in this manual.
Download the new application to the controller and place the processor in run
mode. If you encounter errors, refer to Diagnostics and Troubleshooting (page
51) for information on how to connect to the module's Config/Debug port to use
its troubleshooting features.