5.2.3 PS69 LEDs
The LEDs as shown on the front panel will be used to indicate status information of the
PS69-DPM Master module. Each LED has a specific function during Run, configuration
download, and error indications. The following table shows the reaction of each during these
states for Master and Slave.
LED
Color
State
Description
SYS
Yellow
Flashing cyclic at
1Hz
Device is in boot loader mode and is waiting for firmware
download.
Yellow
Flashing cyclic at
5Hz
Firmware download is in progress.
Yellow
Flashing irregular (*) Hardware or runtime error detected.
Green
Static On
Communication is running. The device has established at
least one configured fieldbus connection.
Green
Flashing cyclic at
5Hz
No error in configuration found, communication is stopped.
Green
Flashing irregular (*) Power Up: Configuration missing or faulty, device needs
commissioning.
Runtime: Host Watchdog timeout
Off
Off
Device has no power supply or hardware defect.
COM
Green
On
Device is holding the PROFIBUS token and is able to transmit
telegrams.
Green
Flashing acyclic (**)
Device is sharing the PROFIBUS token with other master
devices in the PROFIBUS network.
Red
On
Device has found a communication problem to at least one
PROFIBUS-DP slave device or has detected a short circuit.
Off
Off
Device is not configured or has not received the Token
permission on the PROFIBUS network.
(*) 3 times fast at 5 Hz, 8 times between 0,5Hz and 1Hz
(**) between 0,5Hz and 100Hz