Contents
PS69-DPM ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 64 of 130
ProSoft Technology, Inc.
October 1, 2014
GLOBAL-BITS
Bit Offset
Member Name
Data Type
Signification
Meaning if Bit is set
0
Ctrl
BOOL
CONTROL-ERROR Parameterization error
1
Aclr
BOOL
AUTO-CLEAR-
ERROR
Module stopped communication
with all slaves and reached the
auto-clear-end state.
2
Nexc
BOOL
NON-EXCHANGE-
ERROR
At least one slave has not reached
the data exchange state and no
process data will be exchanged.
3
Fat
BOOL
FATAL-ERROR
Because of major bus error, no
further bus communication is
possible.
4
Eve
BOOL
EVENT-ERROR
The module has detected bus short
circuits. The number of detected
events is contained in the
Bus_error_cnt variable. This bit is
set when the first event was
detected and will remain set.
5
NRdy
BOOL
HOST-NOT-
READY-
NOTIFICATION
Indicates if the Application program
has set its state to operative or not.
If this bit is set the Application
program is not ready to
communicate
6
Tout
BOOL
TIMEOUT-ERROR The module has detected an
overstepped timeout supervision
value because of rejected
PROFIBUS telegrams. It is an
indication for bus short circuits
while the master interrupts the
communication. The number of
detected timeouts is available in
the Time_out_cnt variable. This bit
will be set when the first timeout is
detected and will remain set.
7
Reserved1
BOOL
Reserved
Reserved
ERROR-EVENT Codes for an Err_Rem_adr of 255
Code
Indication
Source
Corrective Action
0
No errors
None
None.
50
USR_INTF-Task Not Found
Master
Firmware is invalid. Module must be
updated.
51
No Global Data
Master
Firmware is invalid. Module must be
updated.
52
FDL-Task Not Found
Master
Firmware is invalid. Module must be
updated.
53
PLC-Task Not Found
Master
Firmware is invalid. Module must be
updated.
54
Non Existing Master Parameters
Master
Execute download of configuration
database again.
55
Faulty Parameter Value in the
Master Parameters
Configuration
Firmware is invalid. Module must be
updated.