ProSoft Technology PS69-DPM User Manual
Page 89
PS69-DPM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 89 of 130
October 1, 2014
Failure
Significance
Error source
Help
17 =
CON_NA
No response of the station
Slave
Check network wiring, check bus address of
Slave or baud rate support
18 =
CON_DS
Master not into the logical token ring Network in general Check master DP address or highest-station-
address of other Masters. Examine bus wiring
for bus short circuits.
54 =
CON_AD
Negative response received, access
denied
Slave
access denied
MSAC1_Read and MSAC1_Write
Failure
Significance
Error source Help
0 = CON_OK
Service was executed without an
error
2 = CON_RR
Resource unavailable
Slave
Slave has no buffer space left for the
requested service
3 = CON_RS
Requested function of master is not
activated within the slave
Slave
Slave is not activated in its DPV1support
9 = CON_NR
No answer-data, although the slave
has to response with data
Slave
Slave has not sent any data back
17 = CON_NA
No response of the station
Slave
Check network wiring, check bus address of
Slave or baud rate support
18 = CON_DS
Master not into the logical token ring Network in
general
Check Master DP address or highest-station-
address of other Masters. Examine bus wiring
to bus short circuits
25 = CON_NP
No plausible reaction of remote
partner
Slave
Slave does not conform to DPV1 norm
54 = CON_AD
Negative response received, access
denied
Slave
Access denied to requested data. Check
Error_Code_1 and Error_Code_2 in response
message to get further error information
81 hex =
REJ_SE
DEVICE is about to stop the DPV1-
communication or the DPV1 is not in
OPEN state
HOST,
configuration
DPV1 communications must be configured to
be activated by the DEVICE
82 hex =
REJ_ABORT
DEVICE has stopped the DPV1
communication automatically
Slave
A previously addressed Slave has responded
with non conform parameters
83 hex =
REJ_PS
A previous service is still in process HOST
Wait for the outstanding answer first. Parallel
services are not allowed
84 hex =
REJ_LE
The length indicator msg.data_cnt
exceeds maximum configured size
HOST
Reduce length of message or enlarge
maximum buffer size in PROSOFT.fdt
(SYCON.net) or in SLAVE data set
85 hex = REJ_IV Wrong parameter in request
HOST
Check msg.function or msg.device_adr
parameter of requested message
9a hex =
REJ_COM
Unknown msg.b command
HOST
Correct the requested msg.b parameter of
message