ProSoft Technology PS69-DPM User Manual
Page 85

PS69-DPM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 85 of 130
October 1, 2014
CIP Message Parameters for MSAC1_Write
Parameter
Value
Remarks
Message Type
CIP Generic
Service Type
Custom
Service Code
64 hex
Service Code "Bridge Message"
Class
65 hex
CIP Object "CIP_MSG_BRIDGE""
Instance
1
Attribute
0
Source Element
WriteReq
Reference to a Tag of type MSAC1_WRITE_REQUEST
Destination
WriteCnf
Reference to a Tag of type
MSAC1_WRITE_CONFIRM
Source Length
16 + x
( x = 1 .. 240 )
16 = Constant part of the service MSAC1_WRITE_REQUEST
x = Number of data to be transferred
MSAL1M_Alarm_Res
The MSAL1M_Alarm_Res request is used by the master to send a DPV1 Alarm response to
a slave device. The message acknowledges the alarm when the appropriate indication
appears in theDPV1 Alarm Indication (page 67) area. The information mapped to this area
must be used in the DPV1 Alarm Response message in order to process the alarm properly.
The mapping of this information shall be as follows.
MSAL1M_ALARM_RES_REQUEST
Parameter
Data Type
Value
Description
Reserved1
INT
0
Reserved
Reserved2
INT
0
Reserved
Reserved3
INT
0
Reserved
Command
SINT
18
Command for Service MSAL1M_Alarm_Res
Reserved4
SINT
0
Reserved
DeviceAdr
SINT
0.. 125
Address of the PROFIBUS Slave from DPV1 Alarm Indication
Register.
SlotNum
SINT
0.. 254
Slot Number from DPV1 Alarm Indication Register.
SeqNum
SINT
0.. 31
Sequence Number from DPV1 Alarm Indication Register.
AlarmType
SINT
1 to 6,32 to
126
Alarm Type from DPV1 Alarm Indication Register.
AlarmSpec
SINT
0..7
Alarm Spec from DPV1 Alarm Indication Register.
Reserved5
SINT
0
Reserved