ProSoft Technology PS69-DPM User Manual
Page 77

PS69-DPM ♦ CompactLogix or MicroLogix Platform
Contents
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 77 of 130
October 1, 2014
DDLM_SLAVE_DIAG_REQUEST
Parameter
Data Type
Value
Description
Reserved1
INT
0
Reserved
Reserved2
INT
0
Reserved
Reserved3
INT
0
Reserved
Command
SINT
66
Command for the DDLM_Slave_Diag service
Reserved4
SINT
0
Reserved
DeviceAdr
SINT
0..125
Address of the PROFIBUS Slave
DataArea
SINT
Reserved
DataAdr
INT
Reserved
DataIdx
SINT
Reserved
DataCnt
SINT
Reserved
DataType
SINT
Reserved
Function
SINT
1,3
1 Read the diagnostic information from the internal buffer of
the Master
3 Read the diagnostic information directly from the Slave
DDLM_SLAVE_DIAG_CONFIRM
Name
Data Type
Value
Description
Reserved1
INT
0
Reserved
Reserved2
INT
0
Reserved
Answer
SINT
66
Answer DDLM_Slave_Diag
Failure
SINT
e
Error, Status (see following section)
Reserved3
INT
0
Reserved
DeviceAdr
SINT
0 .. 125
Slave Address
DataArea
SINT
0
Reserved
DataAdr
INT
0
Reserved
DataIdx
SINT
0
Reserved
DataCnt
SINT
6 + x
Length of the diagnostic structure (starting with
StationState_1)
DataType
SINT
0
Reserved
Function
SINT
1,3
Read function
StationState_1
SINT
S1
Station status_1
StationState_2
SINT
S2
Station status_2
StationState_3
SINT
S3
Station status_3
MasterAddress
SINT
MA
Master address
IdentNumber
INT
ID
Ident Number
Reserved4
INT
0
Reserved
ExtDiag[0..99]
SINT
EX
Extended Diagnostic