The maximum length of a bus segment depends on the baud rate used. Only PROFIBUS
certified cable, preferably the cable type A, should be used.
Baud rate in kBit/s
Max. Distance
9.6
1,200 m / 4000 ft
19.2
1,200 m / 4000 ft
93.75
1,200 m / 4000 ft
187.5
1,000 m / 3280 ft
500
400 m / 1300 ft
1,500
200 m / 650 ft
3,000
100 m / 325 ft
6,000
100 m / 325 ft
12,000
100 m / 325 ft
Parameter
Value
Impedance
135 to 65 Ohm
Capacity
< 30 pF/m
Loop resistance
110 Ohm/km
Wire gauge
0.64 mm
6.1.4 Hardware Specifications
Specification
Description
Processor
EC1-160P with integrated ASPC2
PROFIBUS Interface
RS-485, max. 12 MBaud, potential free, according EN
50170
Diagnostic Interface
RS232, PS/2 Mini DIN female connector, 9600 Baud, non
isolated
Power Supply
+5 V ±5 % / 260 mA
Max. Distance Rating
max. 6 modules to the power supply module
Dimensions
Standard 1769 Single-slot module
Burst
EN 61000-4-4, 2 kV, 5 kHz
Surge
EN 61000-4-5, 2 kV common mode, 1 kV differential
mode
ESD
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Radiated/ Conducted
Immunity
EN 61000-4-3, 10 V/m, 30...1000 MHz, 80% AM, 1 kHz
sinewave
EN 61000-4-6, 10 V, 0,15...30 MHz
Radiated/ Conducted
Emission
EN 55011 Class A
Vibration/Shock
IEC 600068-2-6, 10-150 Hz, ± 0,75 mm, ± 1 g, 1
Octave/min
IEC 600068-2-27, 15 g, 11 ms
Operating Temp.
0 to 60°C (32 to 140°F)
Relative Humidity
5 to 95% (non-condensing)