LSICVM01 Kit Quick Installation Guide
September 2014

Installing the LSICVM01 Kit

3.2

Attaching a CVFM02 Module Directly to a MegaRAID Controller

Perform the following tasks to attach the CVFM02 module directly to the MegaRAID SAS 9266-8i RAID controller.

1.

Ground yourself, and make sure that the system is grounded.

2.

Remove the CVFM02 module from the package.

3.

Place the CVFM02 module top-side-up on a flat, clean, static-free surface.

4.

Mount the three standoffs on the front side of the controller by screwing in three screws from the back side of the
controller, as shown in the following figure.

The standoffs are threaded at both ends, and the screws thread from the back side of the controller into the

board-to-board standoffs.

NOTE

Center the screwdriver carefully to avoid stripping the screw heads. Do
not overtighten the

screws.

5.

Hold the CVFM02 module so that the top side is facing up, and the J3L1 connector on the CVFM02 module lines
up with the J4B1 connector on the RAID controller, as shown in the following figure.

Figure

3 Installing the CVFM02 Module on the MegaRAID SAS 9266-8i RAID Controller

6.

Carefully press the CVFM02 module onto the RAID controller so that the two connectors are firmly joined.

7.

Secure the CVFM02 module to the RAID controller by screwing in the three screws from the front side of
the

controller.

The standoffs are threaded at both ends, and the screws thread from the top side of the CVFM02 module into the

board-to-board standoffs.

3_00893-00

J4B1

CacheVault

Flash Module