The Fig. 10 shows states when Graph R(t) is enabled. After taking a measurement, you can switch
back and forth between numerical mode display and graphical mode display by pressing or keys.
graphical mode
numerical mode
Note
• It is not possible to switching mode of presentation when measurement running!!!
Initial display -
numerical mode
Initial display -
graphical mode
Display with results -
numerical mode
Display with results -
graphical mode
Fig. 10 Insulation Resistance function display states - Graph R(t) enabled
Measurement procedure:
• Connect the test leads to the instrument and to the test object.
• Select INSULATION RESISTANCE function in MAIN MENU.
• Press the START/STOP key and release it, continuous measurement will begin.
• Wait until the test result has stabilized then press the START/STOP key again to stop the
measurement or, if enabled, wait for the set timer runs out.
• Wait for the object under test to discharge.
• The result can optionally be saved pressing the MEM key twice, see the description of Store,
Recall and Clear Operation.