Table 8, Liebert nxl module battery disconnect cabinet – Emerson NXL UPS Systems User Manual
Page 42
Specifications
38
Table 8
Liebert NXL Module Battery Disconnect Cabinet
Battery Parameters
Value
Nominal Battery Bus, VDC
480V
Battery Float Voltage, VDC
540V
Minimum EOD
Voltage, VDC
384V (for VRLA / Flooded Lead Acid)
Battery Discharging Max current (EOD), A
Physical Parameters and Standards
Width in. (mm)
without side panels attached
30.9 (785)
Depth, in. (mm)
33.5 (850)
Height,
in. (mm)
76.8
(1950)
Weight, lb (kg) approx.
Color
Charcoal (ZP-0420)
Front Door Opening (for serviceability)
More than 180°
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Standards & Conformities
UL 1778
CSA 22.2 107.3
FCC Part 15, Class A
ISTA Procedure 1H
WEEE
Minimum clearance, Top)
24" (610mm)
Minimum clearance, Back)
0"
Minimum clearance, Sides)
0"
Location of cable entrance
Top or Bottom
Environmental Parameters
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
Relative Humidity
Maximum 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude Above Mean Sea Level, ft (m)
4920 (1500) (as per IEC 62040/3) -
1% Max kW derate / 100m rise between
1500-3000m