Table 8, Liebert nxl module battery disconnect cabinet – Emerson NXL UPS Systems User Manual

Page 42

background image

Specifications

38

Table 8

Liebert NXL Module Battery Disconnect Cabinet

Battery Parameters

Value

Nominal Battery Bus, VDC

480V

Battery Float Voltage, VDC

540V

Minimum EOD

Voltage, VDC

384V (for VRLA / Flooded Lead Acid)

Battery Discharging Max current (EOD), A

See Table 11

Physical Parameters and Standards

Width in. (mm)

without side panels attached

30.9 (785)

Depth, in. (mm)

33.5 (850)

Height,

in. (mm)

76.8

(1950)

Weight, lb (kg) approx.

See Table 14

Color

Charcoal (ZP-0420)

Front Door Opening (for serviceability)

More than 180°

Degree of Protection for UPS Enclosure

IP 20 (with and without front door open)

Standards & Conformities

UL 1778

CSA 22.2 107.3

FCC Part 15, Class A

ISTA Procedure 1H

WEEE

Minimum clearance, Top)

24" (610mm)

Minimum clearance, Back)

0"

Minimum clearance, Sides)

0"

Location of cable entrance

Top or Bottom

Environmental Parameters

Storage Temperature Range, °F (°C)

-13°F to 158°F (-25°C to 70°C)

Operating Temperature Range, °F (°C)

32°F to 104°F (0 to 40°C)

Relative Humidity

Maximum 95% Non-Condensing

(Operating and Non-Operating)

Maximum Altitude Above Mean Sea Level, ft (m)

4920 (1500) (as per IEC 62040/3) -

1% Max kW derate / 100m rise between

1500-3000m