Installation Drawings

35

Figure 33 Alber battery monitoring assembly diagram

Table 6

Alber battery monitoring assembly connections

Input

Voltage

Alber Transformer-2

(Wht)

Jumper

Alber Transformer-1

(Blk)

F4-F5

Fuse Rating

600

0 (Top)

300 (Top) to 0 (Bottom)

300 (Bottom)

2.25 A, 600VAC

480

0 (Top)

240 (Top) to 0 (Bottom)

240 (Bottom)

1.25 A, 600VAC

380

0 (Top)

300 (Top) to 208 (Bottom)

300 (Bottom)

1 A, 600VAC

208

0 (Top)

0 (Top) to 0 (Bottom) and

208 (Top) to 208 (Bottom)

208 (Top)

0.75A, 600VAC

F76

F75

NXL BATTERY CABINET

UPS MODULE OUTPUT

XFMR CONNECTION DIAGRAM

Harness factory-installed.
Verify transformer connection
Prior to startup.
See diagram below.

.

.

AL

BER B

A

T

T

E

R

Y

M

O

NI

T

O

R

ING X

F

M

R

This harness is intended for use only when
battery cabinet is connected directly to UPS.
For all other instances, customer must supply wire.

TOP TERMINALS

FROM F5 FUSE IN BAT CAB

BOTTOM TERMINALS

FROM F4 FUSE IN BAT CAB

250, 300, & 400 KVA UPS MODULE

FUSEBLOCK INSTALLATION

F5

F4

Mount fuses to corner post

in input/output compartment

of UPS module. Choose best

location based on bottom or top

power cabling.

UPS Output - Phase A
Use Pilot Hole on Busbar.

UPS Output - Phase C
Use Pilot Hole on Busbar.

V_OUT_A

V_OUT_C

Wire Harness

Secure supplied wire harness
to busbar with supplied hardwar

Locate fuse label as
close to fuses as possible

Connect cables from UPS output

busbars to fuse block

X1

X2

0 V

270 V

208 V

240 V

300 V

200 V

0 V

270 V

208 V

240 V

300 V

200 V

230 V