Figure 18 wide junction cabinet terminal wiring – Emerson NXL UPS Systems User Manual

Page 25

background image

Installation Drawings

21

Figure 18 Wide junction cabinet terminal wiring

Notes:
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are without side panels. The width is 32.1" (815mm) with side panels.
8.The depth dimension includes the front door and rear panel.

13.7

(348)

Negative Bus

Ground Bus

Positive Bus

Ground
Bus

Negative
Bus

Positive
Bus

9.0

(228)

8.7

(221)

7.4

(189)

.56

(14) Typ

.56

(14) Typ

.56 (14)

Typ

13.6

(346)

Front View

Right Side

View

41.3

(1050)

76.9

(1952)

30.9 (785)

33.5 (805)

2.2 (55)

16 Places

2.2 (55)

18 Places

2.2 (55)

18 Places

2.2 (55)

16 Places

1.7 (44) X 0.7 (18)

Slot 16 Places

Typ. Each Busbar

1.8 (45)

16 Places

2.2 (55)

18 Places