Notice – Emerson NXL UPS Systems User Manual
Page 17
Battery Installation
13
Figure 10 Control cable layout—Liebert NXL UPS to Liebert NXL Battery Cabinet
The CAN cables must be two, twisted pair, shielded 18AWG (Belden 9156 or equivalent). All intercon-
necting cables and hardware for connected and attached cabinets will be provided.
NOTICE
Risk of improper installation. Can cause equipment damage.
During system commissioning, Liebert Services will set the jumpers on the EIB and the BIB.
If another battery cabinet is added to the system after commissioning, it is imperative that
Liebert Services reset the jumpers on the EIB board and the BIB board.
Liebert
NXL
Module
Battery
Disconnect
Cabinet
Additional
Liebert
NXL
Battery
Cabinet
Liebert
NXL
Battery
Cabinet
Liebert
NXL
UPS
Bat. Interface
Board (BIB)
TB1154
Bat. Interface
Board (BIB)
TB1154
Bat. Interface
Board (BIB)
TB1154
Ext. Interface
Board (EIB)
TB1154
CAN Cable
CAN Cable
CAN Cable
Liebert
NXL
Battery
Cabinet
Liebert
NXL
UPS
Additional
Liebert
NXL
Battery
Cabinet
Ext. Interface
Board (EIB)
TB1154
Bat. Interface
Board (BIB)
TB1154
Bat. Interface
Board (BIB)
TB1154
CAN Cable
CAN Cable