Table 5 liebert-supplied interconnect wiring, Battery cabinet, Table 5 – Emerson NXL UPS Systems User Manual
Page 36: Liebert-supplied interconnect wiring

Installation Drawings
32
Figure 30 Liebert NXL UPS to Liebert NXL Module Battery Disconnect to Liebert NXL Battery Cabinet
Table 5
Liebert-supplied interconnect wiring
Run
From
To
Conductors
A1
UPS - DC+ Busbar
MBD - DC+ Busbar
Positive Power - RH Mount/
Stand-Alone
B1
UPS - DC- Busbar
MBD - DC- Busbar
Negative Power - RH Mount/
Stand-Aone
A2
UPS - DC+ Busbar
MBD - DC+ Busbar
Positive Power - Left Mount
B2
UPS - DC- Busbar
MBD - DC- Busbar
Negative Power - Left Mount
C*
UPS - Ground
MBD - Ground
Ground
D
UPS - External Interface
Board (EIB)
MBD - Battery Interface Board (BIB)
CAN Control Cables
E
MBD - DC+ Busbar
Battery Cabinet - DC+ Busbar
Positive Power
F
MBD - DC- Breaker
Battery Cabinet - DC- Busbar
Negative Power
G
MBD - Battery Interface
Board (BIB)
Battery Cabinet - Battery
Interface Board (BIB)
CAN Control Cables
H*
MBD - Ground
Battery Cabinet - Ground
Ground
* For detached units only
Top Feed A1, A2, E
F, B1, B2
C,H
Top
Feed
D,G
G
H
F
E
A1
B1
C
D
UPS - Rear View
DC Bus Connections
F
E
B1,2 Bottom
Feed
F
C,H
Bottom
Feed
Bottom
Feed
A1,2,E
A2
B2
Top
Feed
UPS
Battery Cabinet
Modular Battery Disconnect