Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual
Page 67
67
P
ROBLEM SOLVING
Commands in progress: indicates presence of a remote command in progress.
CODE
DESCRIPTION
C01
Remote shutdown command
C02
Remote load on bypass command
C03
Remote switch-on command
C04
Battery test in progress
LOCK
The LOCK (block) type report signals are usually preceded by an alarm signal and, on account of their
importance, result in the inverter being switched off and the load being powered through the bypass line (the
procedure is excluded in case of lockouts due to strong and persistent overloads and lockouts following a short-
circuit).
CODE
DESCRIPTION
L03
Auxiliary power supply incorrect
L04
High temperature on heat sinks
L05
Temperature Sensor1 broken
L07
Temperature Sensor2 broken
L10
Input fuse broken or input relay stuck (does not close)
L13
Capacitor precharging failure
L20
Capacitor bank undervoltage
L21
Capacitor bank overvoltage
L40
Inverter overvoltage
L41
D-C voltage on output
L42
Inverter voltage not right
L43
Inverter undervoltage
L50
Overload: load > 103%
L51
Overload: load > 110%
L52
Overload: load > 150%
L53
Short-circuit