Riello UPS Sentinel Dual (Low Power) (1000 - 3000 VA) User Manual
Page 22

22
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
EnergyShare
Select the auxiliary socket
operating mode
Always
connected
• Always connected
• Disconnection after no. seconds of battery
operation
• Disconnection after no. seconds of the battery
discharge pre-alarm signal
• ... (see UPStools manual)
Bypass voltage
thresholds
Selects the permitted
voltage range for switching
to the bypass
Low: 180V
High: 264V
• Low: 180 - 200 in 1V steps
• High: 250 - 264 in 1V steps
Bypass voltage
threshold for ECO
Selects the permitted
voltage range for operation
in ECO mode
Low: 200V
High: 253V
• Low: 180 - 220 in 1V steps
• High: 240 - 264 in 1V steps
Intervention
sensitivity for
ECO
Selects the intervention
sensitivity during operation
in ECO mode
Normal
• Low
• Normal
• High
Power-on delay
Waiting time for automatic
switching back on after
mains power returns
5 sec.
• Disabled
• (1 - 255) sec. in 1 sec steps
Remote Switch
on/off feature
Select the feature
associated with the remote
control terminal board.
Pin 1-2 REPO
Pin 2-3 Remote
ON
• Pin 1-2 REPO
• Pin 2-3 Remote ON, Remote ON/OFF