Riello UPS Sentinel Dual (Low Power) (1000 - 3000 VA) User Manual

Page 22

background image

22

FUNCTION

DESCRIPTION

DEFAULT

POSSIBLE CONFIGURATIONS

EnergyShare

Select the auxiliary socket
operating mode

Always

connected

• Always connected

• Disconnection after no. seconds of battery

operation

• Disconnection after no. seconds of the battery

discharge pre-alarm signal

• ... (see UPStools manual)

Bypass voltage

thresholds

Selects the permitted
voltage range for switching
to the bypass

Low: 180V
High: 264V

• Low: 180 - 200 in 1V steps

• High: 250 - 264 in 1V steps

Bypass voltage
threshold for ECO

Selects the permitted
voltage range for operation
in ECO mode

Low: 200V
High: 253V

• Low: 180 - 220 in 1V steps

• High: 240 - 264 in 1V steps

Intervention

sensitivity for

ECO

Selects the intervention
sensitivity during operation
in ECO mode

Normal

• Low

• Normal

• High

Power-on delay

Waiting time for automatic
switching back on after
mains power returns

5 sec.

• Disabled

• (1 - 255) sec. in 1 sec steps

Remote Switch

on/off feature

Select the feature
associated with the remote
control terminal board.

Pin 1-2 REPO

Pin 2-3 Remote

ON

• Pin 1-2 REPO

• Pin 2-3 Remote ON, Remote ON/OFF