New duct systems must leak less than 6% of the air handler’s flow.

Maximum allowable duct tester measurement based on 3 different base system air handler flow is:

For A/C systems multiply the Tonnage X 24 CFM.

Assumes 400 CFM per Ton with maximum allowable leakage of
6% = 24 CFM per Ton.

TONNAGE ___ X 24 = _____
CFM

E.g. a 5 Ton system must have less than 5 X 24 = 120 CFM of leakage at a 25 Pa test pressure in the
supplies.

For Heating systems divide the BTU /1000 X 1.302 CFM.

Assumes 21.7 CFM per 1000 BTU capacity with maximum
allowable leakage of 6% = 1.302 CFM per 1000 BTU.

BTU _________ /1000 X 1.302 =
____CFM

E.g. a 100,000 BTU furnace must less than 100,000 / 1000 X 1.302 = 132 CFM of leakage.

Measure the fan flow divided by 100 X 6.

Measured fan flow ______ / 100 X 6 =
____CFM

E.g. an air-handler blower flow of 2000 CFM must have less than 2000 / 100 X 6 = 120 CFM of leakage.

Existing duct systems must leak less than 15% of the air handler’s flow.

The Maximum allowable duct tester measurement based on 3 different base system air handler flow is:

For A/C systems multiply the Tonnage X 60 CFM.

Assumes 400 CFM per Ton with maximum allowable leakage of 15% = 60
CFM per Ton.

TONNAGE ___ X 60 = _____
CFM

E.g. a 5 Ton system must have less than 5 X 60 = 300 CFM of leakage at a 25 Pa test pressure in the supplies.

For Heating systems divide the BTU /1000 X 3.255 CFM.

Assumes 21.7 CFM per 1000 BTU capacity with maximum allowable leakage
of 15% = 1.302 CFM per 1000 BTU.

BTU _________ /1000 X 3.255 =
____CFM

E.g. a 100,000 BTU furnace must have less than 100,000 / 1000 X 3.255 = 326 CFM of leakage.

Measure the fan flow divided by 100 X 15.

Measured fan flow ______ / 100 X 15 =
____CFM

E.g. an air-handler blower flow of 2000 CFM must have less than 2000 / 100 X 15 = 300 CFM of leakage.